PAI 6203
AIR/AIR HEAT EXCHANGERS
20-100 W/°C
Our PAI 6203 (IP 54 / IP 34) Series εCOOL Air/Air Heat Exchangers are ideal for the replacement of a Filterfan® solution when the ambient air is too contaminated to enter the cabinet. The εCOOL Air/Air Heat Exchanger feature an energy efficient, minimal maintenance design that is a proven solution in harsh environments. Cover: galvanized/electrostatically powder coated (200 °C); Housing: galvanized sheet steel
Features
Energy Efficient
Ambient air is used for the thermal management of the enclosure.
Maintenance Free
Complete separation of the internal and external air flow and robust steel construction adapted to most environments (dust, solid particulate, vapors … ).
Rugged Design
One piece steel cover design for manufacturing environments which protects internal components.
Easy Electrical Installation
Pluggable connection allows for wiring to be done before the unit is installed.
Space Saving Integrated Design
Units have minimal depth off enclosure making door mounting feasible.
Easy Mechanical Installation
Tool free mounting. Can be mounted by one person with our spring plate design. This unit also features a mounting-friendly seal, no elaborate reworking of the mounting cut-out.
Optimized Airflow Design
Long air path design efficiently delivers cool air below the critical components while removing damaging hot air from the top of the enclosure. The high volume of air flow will eliminate hot spots.
Filterless Design
Maintenance time can be minimized due to the wider fin spacing of the heat exchanger. If required a filter can be added to the unit at any time for more protection in harsh environments.
Reduced Fan Maintenance
Life expectancy of fans exceed industry standards. When replacement is required both fans can be removed from exterior to avoid lock out for maintenance and reduced MTTR.
Integrated Thermostats
Primary mechanical thermostat can be used to adjust temperature, saving energy. The secondary thermostat can be used as an independent alarm set point.
Technical Data Overview
Performance Curve
Cooling capacity Qv [W]
Additional Data
AMBIENT TEMPERATURE RANGE | - 13°F … + 131°F / + - - 25°C … + 55°C |
|
CONTROL RANGE (adjustable) | Control Thermostat | + 68°F … + 131°F / + 20°C … + 55°C; factory setting + 95°F / + 35°C |
Alarm Thermostat | + 86°F … + 149°F / + 30°C … + 65°C; factory setting + 113°F / + 45°C | |
PROTECTION SYSTEM ACCORDING TO EN 60529 | IP 54 | towards the electrical enclosure if used as intended by the manufacturer |
IP 34 | towards the surroundings if used as intended by the manufacturer |
Subject to technical amendments and misprints.
Latest Posts
- Crafting Proactive Thermal Management Plans for Electrical EnclosuresSeptember 3, 2024 - 8:52 AM
- 3D-Coverage Enhances Fire Safety with Performance-Based Standards for Emergency SignalingAugust 26, 2024 - 8:55 AM
- Pfannenberg USA Launches X-Series Cooling UnitsJune 19, 2024 - 9:01 AM